++++Standards and specifications:
IEC60694 The commo n technical requirements of high voltage switchgear and controlgear++++Service conditions:
a. Ambient temperature: Maximum temperature:+40℃ Mini-mum temperature: -15℃
b. Ambient humidity: Daily average RH no more than 95%;Monthly average RH no more than 90%
c. Altitude no higher than 2500m;
d. The air around without any pollution of duty,smoke,ercode or flammable air,steam or salty fog;
++++Main technical specifications:
No. |
Item |
Unit |
Parameters |
|
1 |
Rated Voltage |
KV |
36 |
40.5 |
2 |
Rated Frequency |
Hz |
50/60 |
|
3 |
Rated Current |
A |
630 1250 1600 2000 2500 3150 |
|
4 |
Branch busbar rated current |
A |
630 1250 1600 2000 2500 3150 |
|
5 |
Main busbar rated current |
A |
630 1250 1600 2000 2500 3150 |
|
6 |
1min power frequency withstand voltage |
KV |
70 |
95 |
7 |
Lightening impulse withstand voltage |
kV |
170 |
185 |
8 |
Rated Short-time Withstand Current (4s) |
kA |
20/25/31.5/40 |
|
9 |
Rated Short Circuit Breaking Current(Peak) |
kA |
40/50/63/80/100 |
|
10 |
Protection type |
|
IP4X for housing |
|
11 |
Rated voltage for control Circuit |
V |
DC110, DC220, AC220 |